Anj Anj

Trolly Mobile End Suction Diesel Fire Fighting Water Pump

Customization: Available
After-sales Service: Worldwide
Warranty: 1 Year

Product Description

Basic Specifications

Model NO.:XBC-IS
Type:Self-priming Pump With Inner Recirculation
Engine Type:Diesel Engine
Theory:Gas-hydraulic Hybrid Type
Transmission:Direct Connection
Structure:The Slide
Pump Category:Fire Fighting Pump
Working Pump:End Suction Pump
Package:Wood Case
HS Code:841330900
Trolly Mobile End Suction Diesel Fire Fighting Water Pump

The XBC series diesel engine fire pump set is developed in accordance with national standards for fire pump performance and test methods, as well as the American Fire Protection Association standard NFPA20 for centrifugal fire pump installation. Designed for emergency safety, this system ensures that when building power fails, the diesel emergency pump automatically takes over to safeguard life and property.

These engines feature excellent starting characteristics, strong overload capacity, compact structure, and high automation, making them reliable equipment for critical fire-fighting scenarios.

Diesel Fire Pump Unit

Applications & Key Features

Ideal for emergency water supply in field drainage, high-rise buildings, water companies, steel plants, chemical facilities, hotels, and hospitals.

High degree of automation
Complete protection functions
Reasonable & compact structure
Simple installation process
High-cost performance
Advanced Control cabinet
Four-wheel mobile trolley
Optional rain cover for outdoor use
Mobile Water Pump

Technical Parameters

Technical Specs Chart
Diesel Engine Pump Rate Flow (m3/h) Rate Head (m) Speed (r/min) Pump Type
XBC8.0/13.930-50-6084-80-752900IS80-50-250
XBC7.0/13.047702900IS80-50-250A
XBC6.0/12.244602900IS80-50-250B
XBC12.5/13.930-50-60128-125-1232900IS80-50-315
XBC8.0/27.860-100-12087-80-752900IS100-65-250
XBC5.0/55.6120-200-24058-50-452900IS125-100-200

Operation Modes & Safeguards

(1) Three Start Modes: Manual, Automatic Interlink, and Emergency Manual Direct Start.
(2) Automatic Run: Diesel engine starts automatically if the electric fire pump fails or power is lost.
(3) Self-Charging: Batteries are charged via an industrial power diesel engine charging motor.
(4) Protection System: Warning for 3-fail starts, overspeed, low oil pressure, high water temperature, and low fuel level.
Internal Components

Troubleshooting Guide

Fault Cause Solution
No water suction / Vibration Insufficient water pouring; Pipe leak; Suction too high Check bottom valve; Tighten parts; Reduce suction height
High vacuum / No suction Bottom valve jammed; High resistance; Filter jammed Check valve; Replace pipe; Clean filter
Low Flow Outcome Air sucked; Water level drops; Impeller jammed Clear leak; Increase submerged depth; Clean impeller

System Configuration

Pump Options: IS (single-stage), S/SOW (dual-suction), TSWA/D (multi-stage).
Engines: Available in 1 to 12 cylinder configurations.
Accessories: Filter, fuel tank, storage battery, charger, and preheat system (AC220V).
Control: Microcomputer/PLC automatic control cabinets.

Manufacturing Line Certificates
Maintenance & Service:
1. One year or 1000 working hours guarantee (excluding wear parts).
2. 24/7 Technical support via email.
3. Installation guidance and replacement services provided.

Frequently Asked Questions

Q1: What are the main applications for this diesel pump? A1: It is primarily used for fire protection systems, field drainage, high-rise building water supply, and emergency use in industrial plants.
Q2: How does the automatic start system function? A2: The diesel pump automatically triggers if the electric motor pump fails or if there is a power outage during a fire signal.
Q3: Are the storage batteries maintenance-free? A3: Yes, the units are equipped with maintenance-free batteries, eliminating the need for frequent liquid refilling.
Q4: Can the flow and pressure be adjusted? A4: Yes, using mechanical or electronic regulators, you can change the diesel engine rotation speed to adjust head and flow.
Q5: Is the pump suitable for cold environments? A5: Yes, it features an AC220V water preheat system to ensure reliable operation in temperatures below 5°C.
Q6: What delivery methods are available for the pump units? A6: We offer equipment delivery via standard shipping containers or bulk ship methods depending on the order size.